Maintaining Your Landscape
Winterizing
the system:
As the
weather turns cold you will need to protect the system from freezing.
This is done by:
1. Shutting
off the water source
and
2. Draining
the water from the pipes, valves, and backflow prevention device
We make this
process simple for you, by installing gravity fed valves that will
drain all of the necessary components. You will need to locate and
become familiar with the following components of your system in order
to properly winterize it:
A. The
Timer
B.
The Main Shut-Off (Usually at the street or in the basement)
C.
The Valve Manifold (The grey or green plastic valves with all the
wires coming from them)
D.
The Backflow Prevention Device (This is the big brass apparatus)
E.
And if applicable: Mainline Drain Valves
Step One:
The Timer
Simply turn
it to the "Off or Rain Position" and forget about it.
Step Two: The
Main Shut Off
This is the
valve that normally requires the T-handled water key to open and close
it. This needs to be turned 90 degrees clockwise to close it or until
it stops.
Step Three:
The Valve Manifold
Inside your
valve manifold box you will find a "hose-bib" or similar valve that
needs to be opened (counterclockwise) to allow water to escape and air
to enter the system. Leave it open and replace lid on valve box.
Step Four:
Backflow Prevention Device
This is a
very important step. It is probably the most expensive component to
replace in your system, and it can freeze and break. There are a
series of valves on this unit. It is important to leave the two large
handles at the inlet and outlet side of the unit open (These are for
repair purposes only) The only valves you will be opening and closing
are the "petcocks" on the side or bottom of the unit. These require
the use of a flathead screwdriver to turn them. For the winter they
need to be open. They can turn counter or clockwise to reach this
position. You know you have it right if the slot for the screwdriver
is in line with the outlet. Make sure you open all of them (There
should be at least 3 and up to 6 depending on the model)
Step Five:
Mainline Drain Valves
If there is a
considerable distance between the Main Shut-Off and your Valve
Manifold then you may have an additional drain between the two. This
is usually located in a small round valve box. It will be similar to
the valve in the Valve Manifold box. The procedure is the same as
above, open it by turning it counterclockwise and leave it open.
Starting The
System In Spring:
The procedure
for "firing up" the system is essentially the reverse of the above.
You know you have it right if water isn't gushing out of any of the
valves!
It is always
a good idea to replace your battery at the start of each season to
maintain your timer's memory in the event of a power outage.